YepCalc

Voltage Drop Calculator

Find the voltage drop along a wire in volts and as a percent of the supply voltage, and the voltage left at the load. Choose the wire size and material, then enter the voltage, current, and one-way length of a DC, single-phase, or three-phase circuit.

Circuit

System
V

For example, 120, 230, or 240 V.

A

The current the load draws.

Distance from the power source to the load along the wire. The return path is already counted.

Wire

Wire material

Result

Enter Voltage, Current, and One-way length to see the voltage drop.

How to calculate voltage drop

In a DC or single-phase circuit, the current flows out on one wire and back on the other, so the drop counts the wire twice:

Voltage drop = 2 × one-way length × current × wire resistance per length

In a balanced three-phase circuit, the drop between two lines is √3 times the drop along one wire:

Voltage drop = √3 × one-way length × current × wire resistance per length

Percent drop = voltage drop ÷ voltage × 100

Voltage at load = voltage − voltage drop

For example, 12 AWG copper has a resistance of about 1.9706 Ω per 1,000 ft at 75 °C. At 16 A over 100 ft one way, the drop is 2 × 100 × 16 × 1.9706 ÷ 1,000 = 6.31 V, which is 5.25% of 120 V. The calculator uses the unrounded resistance.

How the wire resistance is found

The calculator works out the DC resistance of each wire size from its cross-sectional area and the resistivity of the metal:

Resistance per length = resistivity at 20 °C × (1 + temperature coefficient × (75 − 20)) × 1.02 ÷ area

AC circuits and shared neutrals

For AC circuits, the calculator uses the DC resistance of the wire only. It treats the power factor as 1 and leaves out the reactance of the wire. That's close for small wire and resistive loads like heaters and incandescent lights. For large wire, about 1/0 AWG or 50 mm² and up, or for motor loads, the actual drop can be different from the result.

A 120/240 V circuit with a shared neutral isn't one of the choices. Enter a 240 V load as Single-phase AC at 240 V, since its current goes out on one hot wire and back on the other. Enter a 120 V load as Single-phase AC at 120 V, since its current goes out on a hot wire and back on the neutral.

The NEC (NFPA 70) has an informational note that a voltage drop of no more than 3% on a branch circuit, and no more than 5% on the feeder and branch circuit together, gives reasonable efficiency of operation. It's an explanation, not a rule. The calculator shows this for reference only and doesn't check whether your circuit meets the code.

Examples

120 V branch circuit

A 12 AWG copper circuit at 120 V carries 16 A over 100 ft one way. The drop is 6.31 V (5.25%), leaving 113.69 V at the load. With aluminum wire of the same size, the drop is 10.38 V (8.65%).

240 V circuit

A 6 AWG copper circuit at 240 V carries 50 A over 150 ft one way. The drop is 7.35 V (3.06%), leaving 232.65 V at the load.

12 V DC run

A 10 AWG copper run at 12 V DC carries 20 A over 25 ft one way. The drop is 1.24 V (10.32%), leaving 10.76 V at the load. Low voltage circuits lose a larger share of their voltage over the same wire.

Three-phase feeder

A 4/0 AWG aluminum feeder at 480 V three-phase carries 150 A over 300 ft one way. The drop is 7.80 V (1.63%), leaving 472.20 V.

Metric circuit

A 2.5 mm² copper circuit at 230 V carries 16 A over 30 m one way. The drop is 8.21 V (3.57%), leaving 221.79 V at the load.